Hager JF80612BG 800a Panel Board (6x250a+12x125a Outgoing) Glazed Door
Part No.:
Please note, a Hager JF805E extension box is required for all incomer options
Characteristics
- Comprises of IP3XD enclosure, pan assembly, neutral bar and earth bar.
- Conforms to BS EN 61439-2. InA = 630/800A, Inc = 125A/250A, Icc = 50kA.
- Supplied without incoming kit, one of the incomer kits listed below must be used.
- Form 3B type 2 using outgoing terminal shield (form 3A without terminal shield).
- Removable gland plates are provided top and bottom for ease of installation.
- Switch Disconnector: 630A/800A, MCCB: 400A/630A, Direct connection: 800A.
- Incoming cable lugged via M12 hexagonal bolt.
Cable Capacity Incomers & Outgoers
- Incomers: 400A: 2 x 240mm², 630A/800A: 2 x 240mm² / 2 x 300mm².
- Outgoers: X160 devices: up to 125A - 70mm² flexible, 95mm² solid,
X250 devices: 150mm2 rigid cables, palm lug max. width: 25mm
Outgoing MCCBs
- X160 adjustable thermal option.
- X250 adjustable thermal / magnetic option.
Dimensions
- Depth of installed product 220 mm
- Height of installed product 1700 mm
- Width of installed product 900 mm
Let us and others know what you think of this product.